High megger reading but a damp motor: the polarization index (IEEE 43)
Short answer
Yes. If insulation is clean and dry, leakage current drops over time; with moisture or dirt it stays high. The polarization index divides the 10-minute insulation resistance reading by the 1-minute one, and IEEE 43 recommends a minimum of 2 for most insulation. If it comes out lower, the winding is cleaned and dried before starting.
Key points
- A high 1-minute reading doesn't prove dry insulation.
- Clean, dry insulation shows leakage current falling over time.
- PI = 10-minute reading divided by 1-minute reading.
- IEEE 43 recommends at least 2 for most insulation.
- Below that, clean and dry before starting.
Transcript
Why can your megger read thousands of megohms and the motor still be damp? It's not the one-minute number, it's how it changes over ten. If the insulation is clean and dry, leakage current drops over time; with moisture or dirt, it stays high. Like a dry sponge versus a wet one: from the outside they look the same. The polarization index divides the 10-minute reading by the 1-minute one, and IEEE 43 recommends a minimum of 2 for most insulation. But careful, if it comes out lower, it's cleaned and dried before starting. So it's not the high reading, it's the trend. Did yours pass the polarization index? Comment MEGGER and we'll tell you what to check.
Frequently asked questions
How is polarization index calculated?
Insulation resistance at 10 minutes divided by the reading at 1 minute.
What minimum does IEEE 43 recommend?
An index of 2 for most insulation systems.
What if it is lower?
Clean and dry the winding before starting. TEMISA tests and dries motors; email ventas@temisa.mx.
Related
Video with images and narration generated with AI.
Request a quotation by email: ventas@temisa.mx. Phone: +52 33 3614 2460.
More videos
- Medium voltage motor rewinding after a ground fault
- Industrial electric motor repair for a volute pump
- Dynamic balancing services for electric motors, ISO 21940
- Squirrel cage rotor repair for broken bars
- Locomotive traction motor repair: the commutator
- Emergency motor repair, on site or in the shop
- Induction motor slip: why it never reaches 1,800 rpm
- Motor starting current: 6 to 7 times rated, for seconds
- Burnout oven in a rewind: keep the core under 360 °C
- Synchronous motor and power factor: a motor that supplies reactive power
- Motor running hot: 10 extra degrees, half the life
- Motor hipot test: why a 4,160 V motor gets 9,320 V
- Form-wound coil surge test: IEEE 522