Electric motor starting current: why it pulls 6 to 7 times rated and doesn't burn
Short answer
At start, with the rotor still, the motor behaves like a shorted transformer and can pull 6 to 7 times its rated current. It doesn't burn because that current drops within seconds as it picks up speed. The risk is starting it again and again back to back: heat builds up in the copper. Respect the manufacturer's starts per hour.
Key points
- With the rotor still, the motor acts like a shorted transformer.
- It can pull 6 to 7 times rated current at start.
- Current drops within seconds as speed builds.
- Back-to-back starts build heat in the copper.
- Respect the manufacturer's starts per hour.
Transcript
Why does a pump motor pull up to 7 times its current at start and not burn up? It's not that it can take anything, it just lasts very little. With the rotor standing still, the motor acts like a shorted transformer. Like running 100 meters all out: you last a few seconds, not all afternoon. It can pull 6 to 7 times its rated current, but it drops within seconds as it picks up speed. But careful, start it again and again back to back, and heat builds up in the copper. Respect the manufacturer's starts per hour. So it's not that it doesn't heat up, it's that you don't give it time. Does yours trip on start? Comment START and we'll tell you what to check.
Frequently asked questions
Why doesn't the motor burn on start?
The high current lasts only seconds and drops as the motor picks up speed.
What happens with repeated starts?
Heat builds up in the copper; respect the manufacturer's starts per hour.
What if the motor trips on start?
Check protection, load and the winding. TEMISA diagnoses and repairs motors; email ventas@temisa.mx.
Related
Video with images and narration generated with AI.
Request a quotation by email: ventas@temisa.mx. Phone: +52 33 3614 2460.
More videos
- Medium voltage motor rewinding after a ground fault
- Industrial electric motor repair for a volute pump
- Dynamic balancing services for electric motors, ISO 21940
- Squirrel cage rotor repair for broken bars
- Locomotive traction motor repair: the commutator
- Emergency motor repair, on site or in the shop
- Induction motor slip: why it never reaches 1,800 rpm
- Burnout oven in a rewind: keep the core under 360 °C
- Synchronous motor and power factor: a motor that supplies reactive power
- High megger, damp motor: what the polarization index shows
- Motor running hot: 10 extra degrees, half the life
- Motor hipot test: why a 4,160 V motor gets 9,320 V
- Form-wound coil surge test: IEEE 522